AKSA APD220A Diesel Generator – 50Hz
AKSA APD220A diesel generator set rated at 220 kVA / 176 kW standby and 200 kVA / 160 kW prime. Powered by an AKSA A6CRX88TI diesel engine, this 400/230V, 50Hz, 3-phase generator is designed for reliable standby and prime power applications, with automatic mains failure control, AKSA AK4160 alternator, integrated fuel tank, electronic governor, and optional sound-attenuated canopy configuration.
Brand: AKSA
Product Overview
The AKSA APD220A is a diesel generating set designed for dependable standby and prime power use across commercial premises, farms, workshops, site cabins, light industrial units, construction sites, and general backup power applications. It delivers 220 kVA / 176 kW standby power and 200 kVA / 160 kW prime power, making it suitable for installations requiring stable 400/230V, 50Hz, 3-phase electrical supply.
Powered by an AKSA A6CRX88TI diesel engine, the APD220A uses a 6-cylinder, turbocharged and intercooled diesel engine designed for medium-duty generator applications. The engine features direct injection fuel system, electronic governor control, replaceable fuel and oil filters, dry element air filter, cooling radiator and fan, starter battery system, flexible fuel connection hoses, industrial exhaust silencer, and 12/24V DC starter and charge alternator support.
The generator is supplied with an AKSA AK4160 alternator designed for stable 3-phase output in standby and prime power applications. The alternator system includes self-excited control, automatic voltage regulation, Class H insulation, and low waveform distortion performance for commercial, agricultural, construction, light industrial, and backup power loads.
Control and protection are handled by an automatic mains failure controller, listed as DSE6020 or DSE6120 depending on regional configuration. The controller supports generator monitoring, mains monitoring, current protection, power monitoring, battery voltage monitoring, alarms, shutdown protection, event logging, and operating status display. The APD220A is available in open or sound-attenuated canopy configuration depending on installation requirements.
Key features
- 220 kVA / 176 kW standby power
- 200 kVA / 160 kW prime power
- AKSA A6CRX88TI diesel engine
- 400/230V, 50Hz, 3-phase output
- 1500rpm engine speed
- 0.8 power factor
- 6-cylinder diesel engine
- Turbocharged and intercooled engine design
- Direct injection fuel system
- Electronic governor system
- AKSA AK4160 alternator
- Self-excited alternator control system
- Automatic voltage regulation
- Class H alternator insulation
- Automatic mains failure control system
- Integrated base fuel tank
- Heavy-duty fabricated steel base frame
- Factory-tested with full-load, control, and safety shutdown checks
- Open or sound-attenuated canopy configuration
- Suitable for standby, prime, commercial, agricultural, workshop, construction, light industrial, and site power use
Technical summary
| Specification | Details |
|---|---|
| Manufacturer | AKSA Power Generation |
| Model | APD220A |
| Fuel type | Diesel |
| Standby power | 220 kVA / 176 kW |
| Prime power | 200 kVA / 160 kW |
| Standby current | 317 A |
| Voltage | 400/230V |
| Frequency | 50Hz |
| Phase | 3 Phase |
| Power factor | 0.8 |
| Engine | AKSA A6CRX88TI |
| Engine speed | 1500rpm |
| Cylinders | 6 in-line |
| Aspiration | Turbocharged and intercooled |
| Cooling | Water cooled |
| Fuel system | Direct injection |
| Governor | Electronic |
| Fuel consumption at standby load | 47.1 L/hr |
| Fuel consumption at prime full load | 42.5 L/hr |
| Fuel consumption at 75% prime load | 32.0 L/hr |
| Fuel consumption at 50% prime load | 21.5 L/hr |
| Fuel consumption at 25% prime load | 11.5 L/hr |
| Fuel tank capacity | 526 L |
| Oil capacity | 24 L |
| Coolant capacity | 23 L engine only |
| Alternator | AKSA AK4160 |
| Alternator standard | BS EN 60034 |
| Alternator control system | Self excited |
| AVR | SX460 |
| Voltage regulation | ?1.5% |
| Insulation class | Class H |
| Protection class | IP22 |
| Stator winding | Double layer concentric |
| Winding pitch | Two thirds |
| Telephone harmonic factor | < 2% |
| Waveform distortion | No load < 1.5% |
| Control panel | DSE6020 / DSE6120 depending on regional configuration |
| Controller type | Automatic mains failure control |
| Open set dimensions | 2900 ? 1400 ? 2045 mm |
| Open set dry weight | 2645 kg |
| Open set fuel tank capacity | 526 L |
| Sound-attenuated dimensions | 3900 ? 1463 ? 2166 mm |
| Sound-attenuated dry weight | 3080 kg |
| Sound-attenuated fuel tank capacity | 526 L |
| Sound pressure level | 82 dB(A) at 7m |
| Configuration options | Open or sound-attenuated canopy |
| Standby KVA | 201-400 KVA |
|---|