AKSA APD135A Diesel Generator – 50Hz

AKSA APD135A diesel generator set rated at 135 kVA / 108 kW standby and 122 kVA / 97.6 kW prime. Powered by an AKSA A4CRX48TI diesel engine, this 400/230V, 50Hz, 3-phase generator is designed for reliable standby and prime power applications, with DSE6120 control, brushless alternator, integrated fuel tank, electronic governor, and optional sound-attenuated canopy configuration.

Brand: AKSA

Product Overview

The AKSA APD135A is a diesel generating set designed for dependable standby and prime power use across commercial premises, farms, workshops, site cabins, light industrial units, construction sites, and general backup power applications. It delivers 135 kVA / 108 kW standby power and 122 kVA / 97.6 kW prime power, making it suitable for installations requiring stable 400/230V, 50Hz, 3-phase electrical supply.

Powered by an AKSA A4CRX48TI diesel engine, the APD135A uses a 4-cylinder, 4.75-litre, in-line diesel engine running at 1500rpm. The engine is turbocharged with air-to-air intercooling, water cooled, and fitted with direct injection fuel system, electronic governor control, replaceable fuel filter, oil filter, dry element air filter, cooling radiator and fan, starter battery system, flexible fuel connection hoses, manual oil sump drain valve, industrial exhaust silencer, steel bellows, and a 12/24V DC starter and charge alternator system.

The generator is supplied with a brushless single-bearing alternator with revolving field design, 2/3 pitch stator, flexible disc rotor, Class H insulation, self-excitation, self-regulation, solid-state automatic voltage regulation, and direct-drive centrifugal blower cooling. This supports stable electrical output for standby and prime power loads.

Control and protection are handled by the DSE6120 control panel. The controller monitors mains supply, generator voltage, current, frequency, engine oil pressure, coolant temperature, battery voltage, running hours, alarms, and shutdown conditions. The APD135A is available in open or sound-attenuated canopy configuration depending on installation requirements.

Key features

  • 135 kVA / 108 kW standby power
  • 122 kVA / 97.6 kW prime power
  • AKSA A4CRX48TI diesel engine
  • 400/230V, 50Hz, 3-phase output
  • 1500rpm engine speed
  • 0.8 power factor
  • 4-cylinder, 4.75-litre in-line diesel engine
  • Turbocharged with air-to-air intercooling
  • Water-cooled engine design
  • Direct injection fuel system
  • Electronic governor system
  • Brushless single-bearing alternator
  • Self-excited and self-regulating alternator system
  • Solid-state automatic voltage regulator
  • Class H alternator insulation
  • IP21 standard alternator protection; IP22/IP23 available
  • DSE6120 control panel
  • Integrated 180-litre fuel tank
  • Heavy-duty fabricated steel base frame
  • Factory-tested with full-load, control, and safety shutdown checks
  • Open or sound-attenuated canopy configuration
  • Suitable for standby, prime, commercial, agricultural, workshop, construction, light industrial, and site power use

Technical summary

SpecificationDetails
ManufacturerAKSA Power Generation
ModelAPD135A
Fuel typeDiesel
Standby power135 kVA / 108 kW
Prime power122 kVA / 97.6 kW
Voltage400/230V
Frequency50Hz
Phase3 Phase
Power factor0.8
EngineAKSA A4CRX48TI
Engine speed1500rpm
Engine power output119 kWm / 159.5 HP
Cylinders4 in-line
Displacement4.75 litres
Bore x stroke110 ? 125 mm
Compression ratio17:1
AspirationTurbocharged with intercooler, air-to-air
CoolingWater cooled
Fuel systemDirect injection
GovernorElectronic
Starting system12/24V DC starter and charge alternator
Fuel consumption at full load27.7 L/hr
Fuel tank capacity180 L
Oil capacity14 L
Coolant capacity48 L
Radiator cooling air136.2 m?/min
Engine air intake6.66 m?/min
Exhaust gas flow17.34 m?/min
Alternator typeBrushless single bearing, revolving field
Alternator poles4 poles
Stator2/3 pitch
RotorSingle bearing, flexible disc
Exciter typeSelf excited
Alternator coolingDirect drive centrifugal blower fan
Insulation classClass H
Protection classIP21 standard; IP22/IP23 available
AC waveform distortionNo load < 1.5%; non-distorting balanced linear load < 5%
Telephone influence factor< 50 per NEMA MG1-22.43
Telephone harmonic factor< 2%
ControllerDSE6120
Open set dimensions2348 ? 1004 ? 1451 mm
Open set dry weight1350 kg
Sound-attenuated dimensions2600 ? 1058 ? 1681 mm
Sound-attenuated dry weight1648 kg
Configuration optionsOpen, canopy, soundproof canopy, or on-road trailer
Standby KVA

76-200 KVA

Share This Product: