AKSA APD165A Diesel Generator – 50Hz

AKSA APD165A diesel generator set rated at 165 kVA / 132 kW standby and 150 kVA / 120 kW prime. Powered by an AKSA A6CRX65TI diesel engine, this 400/230V, 50Hz, 3-phase generator is designed for reliable standby and prime power applications, with DSE6120 control, brushless alternator, integrated fuel tank, electronic governor, and optional sound-attenuated canopy configuration.

Brand: AKSA

Product Overview

The AKSA APD165A is a diesel generating set designed for dependable standby and prime power use across commercial premises, farms, workshops, site cabins, light industrial units, construction sites, and general backup power applications. It delivers 165 kVA / 132 kW standby power and 150 kVA / 120 kW prime power, making it suitable for installations requiring stable 400/230V, 50Hz, 3-phase electrical supply.

Powered by an AKSA A6CRX65TI diesel engine, the APD165A uses a 6-cylinder, 6.49-litre, in-line diesel engine running at 1500rpm. The engine is turbocharged with intercooler, water cooled, and fitted with direct injection fuel system, electronic governor control, replaceable fuel filter, oil filter, dry element air filter, cooling radiator and fan, starter battery system, flexible fuel connection hoses, manual oil sump drain valve, industrial exhaust silencer, steel bellows, and a 12/24V DC starter and charge alternator system.

The generator is supplied with a brushless single-bearing alternator with revolving field design, 2/3 pitch stator, flexible disc rotor, Class H insulation, self-excitation, self-regulation, solid-state automatic voltage regulation, and direct-drive centrifugal blower cooling. This supports stable electrical output for standby and prime power loads.

Control and protection are handled by the DSE6120 control panel. The controller monitors mains supply, generator voltage, current, frequency, engine oil pressure, coolant temperature, battery voltage, running hours, alarms, and shutdown conditions. The APD165A is available in open or sound-attenuated canopy configuration depending on installation requirements.

Key features

  • 165 kVA / 132 kW standby power
  • 150 kVA / 120 kW prime power
  • AKSA A6CRX65TI diesel engine
  • 400/230V, 50Hz, 3-phase output
  • 1500rpm engine speed
  • 0.8 power factor
  • 6-cylinder, 6.49-litre in-line diesel engine
  • Turbocharged with intercooler
  • Water-cooled engine design
  • Direct injection fuel system
  • Electronic governor system
  • Brushless single-bearing alternator
  • Self-excited and self-regulating alternator system
  • Solid-state automatic voltage regulator
  • Class H alternator insulation
  • IP21 standard alternator protection; IP22/IP23 available
  • DSE6120 control panel
  • Integrated 271-litre fuel tank
  • Heavy-duty fabricated steel base frame
  • Factory-tested with full-load, control, and safety shutdown checks
  • Open or sound-attenuated canopy configuration
  • Suitable for standby, prime, commercial, agricultural, workshop, construction, light industrial, and site power use

Technical summary

SpecificationDetails
ManufacturerAKSA Power Generation
ModelAPD165A
Fuel typeDiesel
Standby power165 kVA / 132 kW
Prime power150 kVA / 120 kW
Voltage400/230V
Frequency50Hz
Phase3 Phase
Power factor0.8
EngineAKSA A6CRX65TI
Engine speed1500rpm
Engine power output145 kWm / 194.4 HP
Cylinders6 in-line
Displacement6.49 litres
Bore x stroke105 ? 125 mm
Compression ratio17:1
AspirationTurbocharged with intercooler
CoolingWater cooled
Fuel systemDirect injection
GovernorElectronic
Starting system12/24V DC starter and charge alternator
Fuel consumption at full load34.3 L/hr
Fuel tank capacity271 L
Oil capacity16 L
Coolant capacity38 L
Radiator cooling air190 m?/min
Engine air intake9.819 m?/min
Exhaust gas flow26.69 m?/min
Alternator typeBrushless single bearing, revolving field
Alternator poles4 poles
Stator2/3 pitch
RotorSingle bearing, flexible disc
Exciter typeSelf excited
Alternator coolingDirect drive centrifugal blower fan
Insulation classClass H
Temperature rise125 – 163?C continuous
Protection classIP21 standard; IP22/IP23 available
AC waveform distortionNo load < 1.5%; non-distorting balanced linear load < 5%
Telephone influence factor< 50 per NEMA MG1-22.43
Telephone harmonic factor< 2%
ControllerDSE6120
Open set dimensions2641 ? 1100 ? 1602 mm
Open set dry weight1610 kg
Sound-attenuated dimensions3265 ? 1163 ? 1858 mm
Sound-attenuated dry weight2000 kg
Configuration optionsOpen, canopy, soundproof canopy, or on-road trailer
Standby KVA

76-200 KVA

Share This Product: