PERKINS APD660P Diesel Generator – 50Hz
AKSA APD660P diesel generator set rated at 660 kVA / 528 kW standby and 600 kVA / 480 kW prime. Powered by a Perkins 2806C-E18TAG1A diesel engine, this 400/230V, 50Hz, 3-phase generator is designed for reliable high-capacity standby and prime power applications, with DSE7320 control, brushless alternator, integrated fuel tank, and optional sound-attenuated canopy configuration.
Brand: PERKINS
Product Overview
The AKSA APD660P is a high-capacity diesel generating set built for dependable standby and prime power use across commercial premises, farms, workshops, construction sites, industrial units, site facilities, and backup power applications. It delivers 660 kVA / 528 kW standby power and 600 kVA / 480 kW prime power, making it suitable for installations that require stable 400/230V, 50Hz, 3-phase electrical supply.
Powered by a Perkins 2806C-E18TAG1A diesel engine, the APD660P uses a 6-cylinder, 18.13-litre, turbocharged and air-to-air charge-cooled diesel engine running at 1500rpm. The engine features direct fuel injection, electronic governor control, replaceable fuel, oil and dry element air filters, cooling radiator and fan, starter battery system, flexible fuel connections, jacket water heater on automatic models, and a 12/24V DC starter and charge alternator system.
The generator is supplied with a brushless single-bearing alternator with revolving field design, 2/3 pitch stator, Class H insulation, self-excitation, self-regulation, solid-state automatic voltage regulation, and direct-drive centrifugal blower cooling. This helps provide stable electrical output for standby and prime power loads.
Control and protection are handled by the DSE7320 control panel. The controller monitors mains supply, generator voltage, current, frequency, engine oil pressure, coolant temperature, battery voltage, running hours, generator kVA, kWh, kW percentage, power factor, alarms, and shutdown conditions. The APD660P is available in open or sound-attenuated canopy configuration depending on installation requirements.
Key features
- 660 kVA / 528 kW standby power
- 600 kVA / 480 kW prime power
- Perkins 2806C-E18TAG1A diesel engine
- 400/230V, 50Hz, 3-phase output
- 1500rpm engine speed
- 0.8 power factor
- 6-cylinder, 18.13-litre diesel engine
- Turbocharged and air-to-air charge cooled
- Water-cooled engine design
- Direct injection fuel system
- Electronic governor system
- Brushless single-bearing alternator
- Self-excited and self-regulating alternator system
- Solid-state automatic voltage regulator
- Class H alternator insulation
- IP21 standard alternator protection; IP22/IP23 available
- DSE7320 control panel
- Integrated 1150-litre fuel tank
- Open or sound-attenuated canopy configuration
- Suitable for standby, prime, commercial, agricultural, workshop, construction, industrial, and site power use
Technical summary
| Specification | Details |
|---|---|
| Manufacturer | AKSA Power Generation |
| Model | APD660P |
| Fuel type | Diesel |
| Standby power | 660 kVA / 528 kW |
| Prime power | 600 kVA / 480 kW |
| Voltage | 400/230V |
| Frequency | 50Hz |
| Phase | 3 Phase |
| Power factor | 0.8 |
| Engine | Perkins 2806C-E18TAG1A |
| Engine speed | 1500rpm |
| Engine power output | 583.8 kWm / 782.6 HP |
| Cylinders | 6 vertical in-line |
| Displacement | 18.13 litres |
| Bore x stroke | 145 ? 183 mm |
| Compression ratio | 14.5:1 |
| Aspiration | Turbocharged and air-to-air charge cooling |
| Cooling | Water cooled |
| Fuel system | Direct injection |
| Governor | Electronic |
| Starting system | 12/24V DC starter and charge alternator |
| Fuel consumption at full load | 129 L/hr |
| Fuel tank capacity | 1150 L |
| Oil capacity | 62 L |
| Coolant capacity | 61 L |
| Radiator cooling air | 702 m?/min |
| Engine air intake | 41 m?/min |
| Exhaust gas flow | 115 m?/min |
| Alternator type | Brushless single bearing, revolving field |
| Alternator poles | 4 poles |
| Stator | 2/3 pitch |
| Rotor | Single bearing, flexible disc |
| Exciter type | Self excited |
| Alternator cooling | Direct drive centrifugal blower fan |
| Insulation class | Class H |
| Protection class | IP21 standard; IP22/IP23 available |
| AC waveform distortion | No load < 1.5%; non-distorting balanced linear load < 5% |
| Telephone influence factor | < 50 per NEMA MG1-22.43 |
| Telephone harmonic factor | < 2% |
| Controller | DSE7320 |
| Open set dimensions | 3450 ? 1800 ? 2178 mm |
| Open set dry weight | 4410 kg |
| Sound-attenuated dimensions | 5409 ? 1856 ? 2654 mm |
| Sound-attenuated dry weight | 5590 kg |
| Configuration options | Open, canopy, soundproof canopy, or on-road trailer |
| Standby KVA | 401-999 KVA |
|---|