MITSUBISHI APD1650M Diesel Generator – 50Hz
AKSA APD1650M diesel generator set rated at 1650 kVA / 1320 kW standby and 1500 kVA / 1200 kW prime. Powered by a Mitsubishi S12R-PTAA2 diesel engine, this 400/231V, 50Hz, 3-phase generator is designed for reliable high-capacity standby and prime power applications, with DSE7320 control, Mecc Alte brushless alternator, electronic governor, integrated fuel tank, and optional sound-attenuated canopy configuration.
Brand: MITSUBISHI
Product Overview
The AKSA APD1650M is a high-capacity diesel generating set built for dependable standby and prime power use across commercial premises, industrial sites, infrastructure facilities, construction projects, agricultural operations, workshops, data centres, and critical backup power applications. It delivers 1650 kVA / 1320 kW standby power and 1500 kVA / 1200 kW prime power, making it suitable for installations that require stable 400/231V, 50Hz, 3-phase electrical supply.
Powered by a Mitsubishi S12R-PTAA2 diesel engine, the APD1650M uses a 12-cylinder, 49.03-litre, V-type diesel engine running at 1500rpm. The engine is turbocharged and aftercooled, with direct injection, electronic governor control, water cooling, dry-type air filtration, 24V DC electrical system, block heater support, and heavy-duty construction for large generator applications.
The generator is supplied with a Mecc Alte ECO 46-1S/4 A alternator rated at 1500 kVA. The alternator features brushless operation, Class H insulation, IP23 protection, DER1 automatic voltage regulator, 0.8 rated power factor, and ?0.5% voltage regulation to support stable electrical output for high-capacity standby and prime power loads.
Control and protection are handled by the DSE7320 control panel. The controller supports generator monitoring, automatic mains failure operation, operating status display, alarm indication, fault protection, and shutdown handling. The APD1650M is available in open or AK 99 sound-attenuated canopy configuration with external removable silencer depending on installation requirements.
Key features
- 1650 kVA / 1320 kW standby power
- 1500 kVA / 1200 kW prime power
- Mitsubishi S12R-PTAA2 diesel engine
- 400/231V, 50Hz, 3-phase output
- 1500rpm engine speed
- 0.8 power factor
- 12-cylinder, 49.03-litre V-type diesel engine
- Turbocharged and aftercooled
- Water-cooled engine design
- Direct injection fuel system
- Electronic governor system
- Mecc Alte ECO 46-1S/4 A alternator
- 1500 kVA alternator rating
- DER1 automatic voltage regulator
- Class H alternator insulation
- IP23 alternator protection
- DSE7320 control panel
- Block heater support
- Open or AK 99 sound-attenuated canopy configuration
- Suitable for standby, prime, commercial, industrial, infrastructure, agricultural, data centre, workshop, and site power use
Technical summary
| Specification | Details |
|---|---|
| Manufacturer | AKSA Power Generation |
| Model | APD1650M |
| Fuel type | Diesel |
| Standby power | 1650 kVA / 1320 kW |
| Prime power | 1500 kVA / 1200 kW |
| Voltage | 400/231V |
| Frequency | 50Hz |
| Phase | 3 Phase |
| Power factor | 0.8 |
| Standby current | 2381.64 A |
| Engine | Mitsubishi S12R-PTAA2 |
| Engine speed | 1500rpm |
| Engine standby power | 1441 kW / 1932 HP |
| Engine prime power | 1314 kW / 1761 HP |
| Cylinders | 12 V-type |
| Displacement | 49.03 litres |
| Bore x stroke | 170 ? 180 mm |
| Compression ratio | 13.5:1 |
| Aspiration | Turbocharged and aftercooled |
| Cooling | Water cooled |
| Injection system | Direct injection |
| Fuel pump type | Mitsubishi PS6x2 in-line |
| Governor | Electronic |
| Operating voltage | 24V DC |
| Battery capacity | 4 ? 143 Ah |
| Charge alternator | 30 A |
| Block heater quantity | 2 |
| Block heater power | 3000 W |
| Fuel consumption at full load | 308 L/hr |
| Fuel consumption at 75% load | 234.2 L/hr |
| Fuel consumption at 50% load | 163.3 L/hr |
| Oil capacity | 180 L |
| Coolant capacity | 33 L engine only / 317 L with radiator |
| Cooling fan air flow | 1800 m?/min |
| Air filter | Dry type |
| Alternator | Mecc Alte ECO 46-1S/4 A |
| Alternator power | 1500 kVA |
| Alternator voltage | 400V |
| Alternator type | Brushless |
| AVR | DER1 |
| Voltage regulation | ?0.5% |
| Insulation class | Class H |
| Protection class | IP23 |
| Alternator cooling air | 135 m?/min |
| Alternator weight | 3010 kg |
| Control panel | DSE7320 |
| Canopy | AK 99 – External Removable Silencer |
| Open set dimensions | 4970 ? 2212 ? 3022 mm |
| Open set dry weight | 11400 kg |
| Open set fuel tank capacity | 2000 L |
| Sound-attenuated dimensions | 9000 ? 2800 ? 3307 mm |
| Sound-attenuated dry weight | 15450 kg |
| Sound-attenuated fuel tank capacity | 2200 L |
| Configuration options | Open, canopy, soundproof canopy, or on-road trailer |
| Standby KVA | 1000 KVA and Over |
|---|