PERKINS APD275P Diesel Generator – 50Hz
AKSA APD275P diesel generator set rated at 275 kVA / 220 kW standby and 250 kVA / 200 kW prime. Powered by a Perkins 1206A-E70TTAG3 diesel engine, this 400/230V, 50Hz, 3-phase generator is designed for reliable standby and prime power applications, with DSE7320 control, brushless alternator, integrated fuel tank, and optional sound-attenuated canopy configuration.
Brand: PERKINS
Product Overview
The AKSA APD275P is a diesel generating set built for dependable standby and prime power use across commercial premises, farms, workshops, construction sites, industrial units, site facilities, and backup power applications. It delivers 275 kVA / 220 kW standby power and 250 kVA / 200 kW prime power, making it suitable for installations that require stable 400/230V, 50Hz, 3-phase electrical supply.
Powered by a Perkins 1206A-E70TTAG3 diesel engine, the APD275P uses a 6-cylinder, 7.01-litre, series turbocharged and aftercooled diesel engine running at 1500rpm. The engine features direct fuel injection, electronic governor control, replaceable fuel, oil and dry element air filters, cooling radiator and fan, starter battery system, flexible fuel connections, and a 12/24V DC starter and charge alternator system.
The generator is supplied with a brushless single-bearing alternator with revolving field design, 2/3 pitch stator, Class H insulation, self-excitation, self-regulation, and direct-drive centrifugal blower cooling. This helps provide stable electrical output for standby and prime power loads.
Control and protection are handled by the DSE7320 control panel. The controller monitors mains supply, generator voltage, current, frequency, engine oil pressure, coolant temperature, battery voltage, running hours, generator kVA, kWh, kW percentage, power factor, alarms, and shutdown conditions. The APD275P is available in open or sound-attenuated canopy configuration depending on installation requirements.
Key features
- 275 kVA / 220 kW standby power
- 250 kVA / 200 kW prime power
- Perkins 1206A-E70TTAG3 diesel engine
- 400/230V, 50Hz, 3-phase output
- 1500rpm engine speed
- 0.8 power factor
- 6-cylinder, 7.01-litre diesel engine
- Series turbocharged and aftercooled
- Water-cooled engine design
- Direct injection fuel system
- Electronic governor system
- Brushless single-bearing alternator
- Self-excited and self-regulating alternator system
- Solid-state automatic voltage regulator
- Class H alternator insulation
- IP21 standard alternator protection; IP22/IP23 available
- DSE7320 control panel
- Integrated fuel tank
- Open or sound-attenuated canopy configuration
- Suitable for standby, prime, commercial, agricultural, workshop, construction, industrial, and site power use
Technical summary
| Specification | Details |
|---|---|
| Manufacturer | AKSA Power Generation |
| Model | APD275P |
| Fuel type | Diesel |
| Standby power | 275 kVA / 220 kW |
| Prime power | 250 kVA / 200 kW |
| Voltage | 400/230V |
| Frequency | 50Hz |
| Phase | 3 Phase |
| Power factor | 0.8 |
| Engine | Perkins 1206A-E70TTAG3 |
| Engine speed | 1500rpm |
| Engine power output | 248.6 kWm / 333.4 HP |
| Cylinders | 6 in-line |
| Displacement | 7.01 litres |
| Bore x stroke | 105 ? 135 mm |
| Compression ratio | 15.8:1 |
| Aspiration | Series turbocharged and aftercooled |
| Cooling | Water cooled |
| Fuel system | Direct injection |
| Governor | Electronic |
| Starting system | 12/24V DC starter and charge alternator |
| Fuel consumption at full load | 56.9 L/hr |
| Fuel tank capacity | 470 L |
| Oil capacity | 16 L |
| Coolant capacity | 25 L |
| Radiator cooling air | 265.2 m?/min |
| Engine air intake | 15.7 m?/min |
| Exhaust gas flow | 33.66 m?/min |
| Alternator type | Brushless single bearing, revolving field |
| Alternator poles | 4 poles |
| Stator | 2/3 pitch |
| Rotor | Single bearing, flexible disc |
| Exciter type | Self excited |
| Alternator cooling | Direct drive centrifugal blower fan |
| Insulation class | Class H |
| Protection class | IP21 standard; IP22/IP23 available |
| AC waveform distortion | No load < 1.5%; non-distorting balanced linear load < 5% |
| Telephone influence factor | < 50 per NEMA MG1-22.43 |
| Telephone harmonic factor | < 2% |
| Controller | DSE7320 |
| Open set dimensions | 2750 ? 1300 ? 1895 mm |
| Open set dry weight | 2080 kg |
| Sound-attenuated dimensions | 3963 ? 1356 ? 2171 mm |
| Sound-attenuated dry weight | 2750 kg |
| Configuration options | Open, canopy, soundproof canopy, or on-road trailer |
| Standby KVA | 201-400 KVA |
|---|