PERKINS APD1875P Diesel Generator – 50Hz
AKSA APD1875P diesel generator set rated at 1875 kVA / 1500 kW standby and 1705 kVA / 1364 kW prime. Powered by a Perkins 4012-46TAG3A diesel engine, this 400/231V, 50Hz, 3-phase generator is designed for reliable high-capacity standby and prime power applications, with InteliGen NT control, Mecc Alte brushless alternator, electronic governor, and optional sound-attenuated canopy configuration.
Brand: PERKINS
Product Overview
The AKSA APD1875P is a high-capacity diesel generating set built for dependable standby and prime power use across commercial premises, industrial sites, infrastructure facilities, construction projects, data centres, agricultural operations, and critical backup power applications. It delivers 1875 kVA / 1500 kW standby power and 1705 kVA / 1364 kW prime power, making it suitable for installations that require stable 400/231V, 50Hz, 3-phase electrical supply.
Powered by a Perkins 4012-46TAG3A diesel engine, the APD1875P uses a 12-cylinder, 45.842-litre, V-type diesel engine running at 1500rpm. The engine is turbocharged, water cooled, and designed for heavy-duty generator applications. It features direct fuel injection, electronic governor control, dry-type air filtration, mechanical fuel pump, 24V DC electrical system, and battery and charge alternator support.
The generator is supplied with a Mecc Alte ECO 46-2S/4 A alternator rated at 1800 kVA. The alternator features brushless operation, Class H insulation, IP23 protection, DER1 automatic voltage regulator, 0.8 rated power factor, and ?0.5% voltage regulation to support stable electrical output for high-capacity standby, prime, and data centre power applications.
Control and protection are handled by the InteliGen NT control panel. The controller is suitable for advanced generator monitoring, automatic start and stop, engine and alternator protection, alarm and shutdown handling, and multi-generator applications where synchronising and power management are required. The APD1875P is available in open or sound-attenuated canopy configuration depending on installation requirements.
Key features
- 1875 kVA / 1500 kW standby power
- 1705 kVA / 1364 kW prime power
- Perkins 4012-46TAG3A diesel engine
- 400/231V, 50Hz, 3-phase output
- 1500rpm engine speed
- 0.8 power factor
- 12-cylinder, 45.842-litre V-type diesel engine
- Turbocharged engine design
- Water-cooled cooling system
- Direct injection fuel system
- Electronic governor system
- Mecc Alte ECO 46-2S/4 A alternator
- 1800 kVA alternator rating
- DER1 automatic voltage regulator
- Class H alternator insulation
- IP23 alternator protection
- InteliGen NT control panel
- Open or sound-attenuated canopy configuration
- Suitable for standby, prime, commercial, industrial, infrastructure, data centre, agricultural, and site power use
Technical summary
| Specification | Details |
|---|---|
| Manufacturer | AKSA Power Generation |
| Model | APD1875P |
| Fuel type | Diesel |
| Standby power | 1875 kVA / 1500 kW |
| Prime power | 1705 kVA / 1364 kW |
| Voltage | 400/231V |
| Frequency | 50Hz |
| Phase | 3 Phase |
| Power factor | 0.8 |
| Standby current | 2706.41 A |
| Prime current | 2461.02 A |
| Engine | Perkins 4012-46TAG3A |
| Engine speed | 1500rpm |
| Engine standby power | 1643 kW / 2202 HP |
| Engine prime power | 1500 kW / 2012 HP |
| Cylinders | 12 V-type |
| Displacement | 45.842 litres |
| Bore x stroke | 160 ? 190 mm |
| Compression ratio | 13.0:1 |
| Aspiration | Turbocharged |
| Cooling | Water cooled |
| Injection system | Direct injection |
| Fuel pump type | Mechanical |
| Governor | Electronic |
| Operating voltage | 24V DC |
| Battery capacity / CCA | 4 ? 143 Ah / 2300 CCA |
| Charge alternator | 40 A |
| Block heater quantity | 2 |
| Block heater power | 3000 W |
| Fuel consumption at full load | 370 L/hr |
| Fuel consumption at 75% load | 275 L/hr |
| Fuel consumption at 50% load | 187 L/hr |
| Oil capacity | 177 L |
| Coolant capacity | 73 L engine only / 339.1 L with radiator |
| Cooling fan air flow | 1905 m?/min |
| Intake air flow | 2083.33 L/s |
| Alternator | Mecc Alte ECO 46-2S/4 A |
| Alternator power | 1800 kVA |
| Alternator voltage | 400V |
| AVR | DER1 |
| Voltage regulation | ?0.5% |
| Insulation class | Class H |
| Protection class | IP23 |
| Control panel | InteliGen NT |
| Open set dimensions | 5212 ? 2074 ? 2835 mm |
| Open set dry weight | 11050 kg |
| Sound-attenuated dimensions | 9000 ? 2800 ? 4246 mm |
| Sound-attenuated dry weight | 14500 kg |
| Configuration options | Open, canopy, soundproof canopy, or trailer |
| Standby KVA | 1000 KVA and Over |
|---|